ISOLATING MODULES
 
GX200

CURRENT LOOP ISOLATING MODULE
WITHOUT AUXILIARY POWER SUPPLY, WITH ENERGY TRANSFER

Model:
  GX200  
  Picture 01  

- 0-20 mA or 4-20 mA signal transfer in the ratio of 1:1
- energy transfer for powering the two-wire converter
- low voltage drop across the module, typically 3.5V
- designed for DIN 35 rail mounting
- conversion accuracy: < 0.2%

      The module is designed to isolate standard current signals, 0 - 20mA, 4 - 20 mA. The supply power is drawn by the module from the input signal. The module can be used to isolate a two-wire converter, which is powered via the 4 - 20mA signal line. If a 0 - 20mA signal is to be isolated, the converter load must be ohmic. The isolation is reached by using a transformer. The input DC signal is chopped to be converted into an AC signal, which is fed into a transformer. It is picked up from the transformer secondary winding and subsequently demodulated to produce a DC signal. The input circuit is protected against noise and polarity reversal. It is also protected against current overload, by means of a resettable thermal cut-out In principle, it is a high-precision DC current transformer. For the same reason, the secondary circuit must be closed for the current passage through the primary winding.

Electrical specifications:
- operating temperature range: -25...+80°C
- storage temperature range: -40...+ 80°C
- maximum supply voltage: 36V
- maximum operating current: 30mA (200mA fuse)
- input: 0/4-20mA
- transfer ratio: 1:1
- transfer function maximum error: < 0,2%
- temperature induced error: < 0,002%/°C
- test voltage: 4000Vr.m.s.
- time constant: < 0,1s
- weight: 90g
     
Type tests:
Standard type test:
EMC:
Safety:
to CSN EN 60770-1
to CSN EN 61326-1
assessed acc. to CSN EN 61010-1

Voltage drop across the module versus input voltage:
 
  Picture 02
 
Terminal designation:
  1,2...input terminals (2 is +)
3,4...output terminals (4 is +)

Dimension sketch:
 
Picture 03

Isolating module application variants:
 

1) Two-wire converter isolation

2) 0 - 20 mA current loop isolation
Picture 04 Picture 05

Ordering instructions:
Your order should include:
- converter type
- quantity (No. of pieces)