ISOLATING MODULES
GXN24 and GXN230 |
ISOLATING MODULES WITH AUXILIARY POWER SUPPLY
GXN24 type ( 24V DC )
GXN230 type ( 230V AC ) - replacing the GON224 type |
Model: |
| |
GXN24 ( GXN230 ) |
|
| |
 |
|
- isolation and mutual conversion of 0 to 20mA, 4 to 20mA and 0 to10V signals
- 18 V DC power supply to power the two-wire converter via input line
- input-to-output-to-power supply isolation: 4000Vr.m.s.
- auxiliary power supply: 24V DC or 230V AC
- DIN 35 rail-mounted design
- conversion accuracy: < 0.2% |
The module is designed to provide isolation and conversion
of standard range currents and/or voltages, namely, 0 to 20mA, 4 to 20mA and 0 to 10V. It can also handle other
DC quantities: voltages from 10mV to 500V, and, currents ranging from 100uA to 500mA. An outlet for the
stabilized power supply, rated 18V/20mA, is situated at the back side of the converter. Typically, the module
can be used as an isolated power supply for a two-wire converter, which is powered via the 4 to 20mA signal line.
The converter output is isolated from both the input and the auxiliary power supply. |
Electrical specifications: |
| - operating temperature range: |
-25...+80°C |
| - storage temperature range: |
-40...+ 80°C |
| - auxiliary power supply |
GXN24: |
24V DC ± 30% |
| |
GXN230: |
230V 50Hz ± 15% |
| - power input: |
max. 2VA |
| - two-wire converter power supply: |
18V při 20mA |
| - input: |
0-20mA, 4-20mA, 0-10V |
| |
any other DC input ranging from |
| |
100uA to 500mA |
| - output: |
0-20mA, 4-20mA, 0-10V or any other |
| - output voltage amplitude: |
min. 15V (R load = 750ohm) at 20mA |
| - voltage output load: |
max. 10mA |
| - input resistance of voltage input: |
typically 100kW / V |
| - output current limit: |
typically 30mA (electronic cut-out) |
| - transfer function maximum error: |
< 0,2% |
| - temperature induced error: |
< 0,01%/°C |
| - input-to-output capacitance: |
20pF |
| - time constant: |
< 0,1s |
| - enclosure: |
casing / terminal board: |
IP40/IP10 |
| - weight: |
90g |
| |
|
|
| Type tests: |
Standard type test:
EMC:
Safety: |
to CSN EN 60770-1
to CSN EN 61326-1
assessed acc. to CSN EN 61010-1 |
| Terminal designation: |
| |
1.....input and power supply minus pole
2.....plus pole for input signal
3.....plus pole of 18V power supply
4,5..output (5 is +)
6,7..auxiliary AC power supply, for (24 VDC, 7 is +) |
Dimension sketch:
|
| |
 |
Isolating module application variants:
|
| |
 |
Ordering instructions:
Your order should include:
- converter type
- input range
- output range
- quantity (No. of pieces) |
|
|