Phone: +420 516 416 942, fax: +420 516 416 963, e-mail:


Czech  Czech version  Polski  Polska verze 

 
 
 
Ikona Page in Acrobat Reader format (127kB)
AC CONVERTERS
 
ACF

AC VOLTAGE FREQUENCY CONVERTER FOR GRID DISTRIBUTION SYSTEMS

Model:
  ACF  
  Picture 01  

- industrial frequency measurement
- auxiliary power supply: 230V 50Hz or 24V DC
- nominal frequencies: 50 or 60 Hz
- input-to-output-to-power supply isolation: 4000Vr.m.s.
- input signal range: within 20 to 120% of rated input
- conversion accuracy: < 0,5%
- compact design
- designed for DIN 35 rail mounting

      The converter has been designed to convert the frequency of an input voltage into a unified DC voltage or current. After the input voltage is shaped and its period compared with that of a precision single-shot trigger circuit, the output voltage is smoother out. It is fed via an isolating optocoupler into the output amplifier. Both the input and the output circuit are overload-protected.
      This converter can be used for handling inputs whose waveforms are distorted. An analog filter is inserted into the converter input securing the converter response being limited to the fundamental frequency only.

Electrical specifications:
- operating temperature range: -25...+80°C
- storage temperature range: -40...+ 80°C
- supply voltage: 24V DC± 30%
  230V ± 15%, 50 - 60Hz, max.2VA
  other options (80..300V DC, 60..250V AC) by arrangement
- protection: resettable thermal cut-out in primary circuit
- rated inputs: 57,7V, 100V, 110V, 220V, 230V, 380V, 400V, 500V AC
- voltage input current load: 0,5mA
- voltage input overload capacity: 2 Unom - 1s
- standard measuring range: 45..55Hz
  48..52Hz
  55..65Hz
  58..62Hz
  other ranges by arrangement
- output: 4-20mA, 0-20mA, 0-10V, ± 10V, ± 5mA, ± 20mA
- output current limit: typically 28mA (electronic cut-out)
- current output maximum load: 15 / Iout (ohm)
- voltage output maximum load: 10mA
- transfer function: linear
- transfer function maximum error: < 0,5%
- temperature induced error: < 0.02%/°C
- test voltage: 4000Vr.m.s.
- output signal settling time: 300ms
- weight: 120g
- enclosure: casing / terminal board: IP40 / IP10
     
Type tests:
Standard type test:
EMC:
Safety:
to CSN EN 60688
to CSN EN 61326-1
assessed acc. to CSN EN 61010-1

Terminal designation:
  1,2...input voltage to be measured
3,4...output terminals (4 is +)
5,6...power supply terminals, polarity insensitive
 

Dimension sketch:
 
  Picture 02

Ordering instructions:
Your order should include:
- converter type
- supply voltage
- rated input voltage
- measuring range (frequency)
- output range
- quantity (No. of pieces)