Phone: +420 516 416 942, fax: +420 516 416 963, e-mail:


Czech  Czech version  Polski  Polska verze 

 
 
 
Ikona Page in Acrobat Reader format (96kB)
TRANSMITTER RTD/4...20mA
 
PMA300

PROGRAMMABLE CONVERTER OF TEMPERATURE

 
PMA300
Obrázek 01

Profile:
  - the device PMA300 can be mounted in the connecting head of the temperature sensor dimension MAA
- simply programming of range by adapter PK-USB without supply (adapter is connect by USB)
- convert temperature from Pt100, Pt1000, Ni100 or Ni1000 sensors to the standard output signal 4-20mA
- suitable for using in industry environment

Electrical specifications:
- input signal: Pt100, Pt1000 by IEC 751 (–55...640°C)
Ni100, Ni1000 (TKR 5000 and 6180) (-40...230°C)

after the agreement it is possible other receptor as NTC and other
- programmable range: from 10°C
- accuracy: conformity error: < 0,3°C
  temperature error: < 0,04°C/10°C
  linearity error: < 0,05% from adjust range (min: 0,1°C for 15 bit and 0,16°C for 14 bit resolution)
  power supply effect: < 50ppm/V in range (max. 0,2°C)
  lead resistance effect: non effect (for 3 wire terminal)/td>
- resolution input/output: 14 or 15bit/12bit
- input connection: 3 or 2 wire (programmable)
- current limitation: short circuit on input:       < 3,2mA
  shut off input: > 22,7mA
- maximal lead resistance: < 20 W / 1 wire
- measuring current: < 0,6mA (mean value)
- damping constant: 0...30 s (smart setting) factory configuration 0,3s
- sampling period <400ms (see table 1)
- working temperature range: -25...+ 80°C
- supply voltage: 8...30V DC in output signal 4-20mA
- output value: 4-20mA
- linear conversion of temperature  
- protection housing / terminal: IP68 / IP10
- connection: wire from 1,5 to 2,5mm2
- dimension: see schema
- programmable adapter USB: PK-USB (free programmable software)
     
Type test:
Basic type test:
EMC:
Safety:
- in compliance with ČSN EN 60770-1
- in compliance with ČSN EN 61326-1
- in compliance with ČSN EN 61010-1

Dimension and connection of device:
+, - :output current loop 4...20mA

Dimension chart PMA300:

Obrázek 02

Installation
  The terminal strips are designed for connecting conductors up to 2,5mm2in cross-section. It is recommended to use a cable with a strand cross-section of 1.5 or 2.5 mm2 in accordance with the required resistance of the line.
  PMA300 are mounted by screw M2,5x15 to the connection head of temperature.
  Leads of sensor be passed through the hole on the side of convertor, then are connected by solder to the pins.

Ordering:
In an order is necessary notify:
 - type of device PMA300
 - number of pieces
 
We can do custom setting, then is necessary notify:
 - type of sensors Pt100, Pt1000, Ni100 or Ni1000 (also TKR)
 - connection of sensor 2W or 3W
 - custom range for instance -10 to 120°C
 - custom damping for instance 0,5s
 - if you don't notify resolution, we set 15 bit