Models: |
| |
NZ124 |
NZ224 |
|
| |
 |
 |
|
The power supplies are intended to power the
converters, isolating modules, converter stem thermometers and other devices in the industry. They
are mounted into switchboxes on a DIN 35 standard electrical equipment mounting rail. |
Type tests: |
Standard type test:
EMC:
Safety: |
to CSN EN 60770-1
to CSN EN 61326-1
assessed acc. to CSN EN 61010-1 |
Electrical specifications: |
| Type |
NZ 124 |
NZ 224 |
| Supply voltage |
230V AC ± 10% ( 45 - 65 Hz ) |
230V AC ± 10% ( 45 - 65 Hz ) |
| Output voltage |
24V DC, ±5% |
24V DC, ±5% |
| Output power capacity |
0,5VA (22mA) |
5VA (200mA) |
| Power input |
1VA |
8VA |
| Protection |
transformer with thermal fuse
electronic cut-out |
transformer with resettable thermal fuse |
| Operation signalling |
green LED diode |
green LED diode |
| Overload signalling |
red LED diode |
none |
| Operating temperature range |
- 25 to + 60°C |
- 25 to + 60°C |
| Enclosure |
casing: IP40, terminal board: IP10 |
casing: IP40, terminal board: IP10 |
Terminal connection: 230V AC
24V DC |
3, 4
1- 2+ |
1, 2
3, 4, 5- 6, 7, 8+ |
|
Device dimensions:
|
| |
 |
| |
 |
Ordering instructions: |
| Examples: |
NZ124, 2 pcs.
NZ224, 1 pc. |
|
|